(2)
Remove two screws and lock washers and open the control panel.
b. Testing.
Tag and unsolder the lead from one end of the resistor and measure the resistance with an ohmmeter. For Model
F10000R6 the resistance should be 50 ohms. For the Model F10000RG-2 variable resistor the maximum resistance
should be 20 ohms. If the correct reading is not obtained, the resistor is defective and must be replaced.
c. Removal.
(1)
Tag and unsolder the remaining lead.
(2)
Remove two screws and lock washers and remove resistor.
d. Installation.
(1)
Secure resistor with two screws and lock washers.
(2)
See wiring diagram figures 45 or 4-6 and tags and solder wire leads.
(3)
Close the control panel door and secure with two screws and lock washers.
(4)
Connect power.
4-38. FUSES
See figure 4-2 or 43.
a. Access.
(1)
Disconnect power.
(2)
Remove two screws and lock washers and open the control panel.
(3)
On the F10000R-6 remove the screw and washer from the pull out disconnect cover and open the cover.
b. Test/Remove.
(1)
On the F10000R-6 there are 4 fuses. F1 is clearly visible in the lower left center of the control box. Fuses
F2, F3 and F4 are located in the pull out disconnect. To gain access to these fuses pull the disconnect portion straight out.
(2)
On the F10000RG-2 there are 2 fuses. Both are clearly visible in the lower right corner of the control box.
(3)
Pull a suspected bad fuse and check it for continuity with an ohmmeter. Replace the fuse if it is bad.
c. Installation.
(1)
Install new fuse.
(2)
If the pull out disconnect (F10000R-6 only) was removed, be sure it is put back in the on position.
(3)
Close the panel(s) and reinstall screws and lock washers.
(4)
Connect power.
4-39. COMPRESSOR MOTOR CONTROLLER (F10000R-6 ONLY )
a. Access.
4-50