Figure 4-31. Alternator Brush Removal F10000RG-2
(3) Now move the one ohmmeter lead from the bracket to the insulated brush. Use an alligator clip directly on the
brush. Be careful not to chip it. Resistance reading should be zero (continuity).
(4)
Connect the ohmmeter leads to the grounded brush and the bracket. Resistance should be zero (continuity).
(5)
Reverse the procedure in (1) above to reinstall the brush.
c. Removal. (See figure 4-30).
(1)
Tag and disconnect the wires from terminals located at the rear of the alternator.
(2)
Loosen the drive belt adjusting bolt and remove the belt from the alternator pulley.
(3)
Remove the adjusting bolt from the adjustment bracket and the mounting and pivot bolt near the lower right
corner.
d. Installation.
(1)
Install, but do not tighten, using the two bolts removed in (3) above.
(2)
Install the drive belt on the pulley, adjust the position of the alternator to achieve proper tension in belt, and
tighten the two bolts. Proper tension in the belt is achieved by obtaining a deflection of 1/2 inch midway between the two
(3)
See tags and wiring diagram figure 46. Reconnect the wires to the terminals on the back of the alternator.
(4)
Close access doors and connect power.
4-62. AIR CLEANER (F10000RG-2)
a. Access.
(1)
Be sure that the unit is turned off. If there is a chance that someone will turn it on, disconnect the battery.