| ||||||||||
| 
 
  | 
![]() TM5-4110-234-14 
TO 40R7-5-7-1 
5-21. MOISTURE INDICATING REFRIGERANT SIGHT GLASS See figure 2-3 for functional description and figure 5-5 
a. 
Removal. 
(1) 
Pump the system down in accordance with paragraph 5-6. 
(2)  Connect a dry nitrogen source to the compressor discharge service tee and loosen the flare nut to the 
receiver inlet valve. Purge this section of tubing in accordance with paragraph 5-9. 
(3) 
Debraze (see para 5-12) the tubes to the sight glass and remove the sight glass. 
b. 
Installation. 
(1) Braze (see para 5-12) the tubes to the sight glass. 
(2) Tighten the flare nut to the receiver inlet valve and remove the nitrogen source. 
(3) Replace the drier (see para 5-19). 
(4) Leak test the sight glass area per paragraph 5-7. 
(5) Evacuate and charge the system as directed in paragraphs 5-10 and 5-11a. 
(6) Close all access doors. 
5-22. 
a. 
Access. Remove the evaporator air housing and screen. (See figure 4-12.) 
b.  Adjust. (See figure 58.) The expansion valve, as supplied with the unit, is preset at the factory. This valve 
should not be adjusted unnecessarily. When a new valve is installed or adjustment is necessary, see the following 
instructions: 
Figure 5-8. Expansion Valve 
5-21 
 | 
| 
 
 Privacy Statement - Press Release - Copyright Information. - Contact Us  |