TM 5-4110-240-13&P
Section IV. TROUBLESHOOTING
4-9.
This table lists the common malfunctions which you may find during the operation or maintenance of the
refrigerator or its components. You should perform the tests/inspections and corrective actions in the order listed.
This manual cannot list all malfunctions that may occur; nor all tests and inspections or corrective actions. If a
malfunction is not listed or is not corrected by listed corrective actions, notify your supervisor. Only those checks
and corrective v X actions which are authorized for organizational maintenance are listed.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
VAPOR PROOF LIGHT WORKS, PILOT LIG HT FAILS, WHEN SWITCH IS SET TO ON.
Step 1
Visually check and replace bulb if required.
Step 2.
Use an ohmmeter to check continuity of wire between pilot light socket and
receptacle.
Replace wire, if defective, in accordance with instructions in Section V,
Organizational Maintenance Procedures.
Step 3
Test pilot light socket using instructions in Section V, Organizational Maintenance
Procedures.
Replace pilot light socket, if defective.
4-6