Order this information in Print

Order this information on CD-ROM

Download in PDF Format

     

Click here to make tpub.com your Home Page

Page Title: Section I. REFRIGERATION SYSTEM
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

C H A P T E R    6 REPAIR   INSTRUCTIONS Section   I. REFRIGERATION   SYSTEM 6-1.  General The   refrigerant   system,   illustrated   by   the refrigerant flow diagram (fig. 5-1), is a mechanical, vapor   cycle-type   circuit   consisting   of   the evaporator,   thermal   expansion   valve,   motor compressor,   condenser   and   the   necessary   valves and   cutout   devices   for   automatic   control   during operation.  The  thermal  expansion  valve  releases high-pressure liquid refrigerant into the evaporator at  reduced  pressure.  The  liquid  refrigerant  begins to vaporize by absorbing heat from the air passing over  the  external  surface  of  the  evaporator  core. The  heated  vapor  is  sucked  out  of  the  evaporator suction  by  the  motor  compressor  and  forced  into the condenser section under high pressure where it is  cooled  and  condensed  back  into  a  liquid.  The heat released during condensation is carried off by the  condensing  air  stream.  The  liquid  refrigerant flows  from  the  condenser  to  a  receiver,  to  a  sub- cooler, and then to the thermal expansion valve. If the  temperature  control  switch  (evaporator  return air thermostat ) becomes satisfied, or the evaporator return  air  temperature  is  lower  than  the  control switch set point, the refrigerant system will switch to  a  by-pass  condition.  The  temperature  control switch  will  activate  the  normally  open  bypass solenoid   valve,   closing   the   valve,   and   therefore shutting off the evaporator section of the unit. The motor  compressor  will  continue  to  pump  as  usual and the suction pressure will begin to drop. When it reaches   approximately   65   psig,   the   pressure regulating  valves  will  start  to  open  in  an  effort  to maintain  the  suction  pressure  above  55  psig (approx.).   As   the   suction   temperature   increases, due to the pressure regulating valves opening, the quench  expansion  valve  will  start  to  meter  liquid refrigerant   into   the   suction   line   in   an   effort   to maintain   the   suction   temperature   below   75°F (approx.) or 30° F superheat (approx.). This action (the pressure regulating and quench valve actions) is totally automatic and also may occur at extreme conditions  in  an  attempt  to  maintain  the  suction pressures  (even  during  the  cooling  mode)  at  a condition   above   55   psig   and   the   suction   tem- peratures  (measured  at  the  quench  bulb  well) below   75°   F.   When   the   compressor   stops,   the equalizer solenoid valve de-energizes and assure es its normal open position, thus allowing pressure to equalize from the discharge line to the suction side of   the   compressor.   To   determine   if   the   valve   is good,  check  for  continuity  or  ground,  by  using  an ohmmeter.  It  should  read  a  resistance  of  40  ohms. The condenser louvers are operated by a refrigerant powered piston located in high pressure part of the system.  This  piston  should  be  fully  extended (louvers  open  80°  approx.)  at  250  psig  head pressure  and  fully  closed  at  165  psig.  Failure  to perform  this  function  could  result  in  icing  of  the evaporator coil and / or cutout on the low pressure cutout. 6-2.  Pressure  Testing  the  Refrigerant  System a. General. A pressure test will indicate whether the  air  conditioner  is  operating  at  normal  or  ab- normal  pressures.  When  the  air  conditioner  is  not operating at normal pressures, the cause should be ascertained  and  corrected.  Refer  to  table  5-1  for troubleshooting  chart. b. System Pressure Test.  Remove caps from high and low pressure charging valves (fig. 5-7). Correct suction   and   discharge   pressure   gages   to   their respective   charging   valves.   Compare   the   gage reading  with  the  normal  range  of  system  pressure shown  in  Table  6-1. Table 6-1. Normal Operating Pressures OUTDOOR  AMBIENT  —  DEGREES  F 6 - 1

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business