TM 5-4120-273-15
each end and tape these ends with electrical tape.
probes of a multimeter to each end of the wire. If
Install a new wire and attach it to the outside. of
continuity is not indicated, the wire is defective
the wiring harness.
and must be repaired or replaced.
d. Repair. Remove the insulation on the wire
to expose one-half inch of bard wire at both ends
The refrigerant piping used on the air condition-
of the break. Twist bare wire together and solder
ing units consists of copper tubing and necessary
the connection. Cover the repaired break with
fittings. Joints of refrigeration pipes and fittings
electrical tape and friction tape. Do not leave any
are soldered. Inspect the piping and fittings for
bare wire exposed. If a terminal lug breaks off a
cracks and breaks (para 3-45b). Replace defective
wire, replace it, using an exact duplicate terminal
lug.
pipes with those of the same length, size, shape,
and material. When soldering or unsoldering
e. Replacement. Replace a wire by disconnect-
items such as the thermostatic expansion valves or
ing it from the component or components and re-
solenoid valves, disassemble the valve and wrap
move the wire. Install a new wire and connect it
valve body with a damp cloth to protect it from
to the component or components. If a broken wire
damage by heat.
is part of a wiring harness, disconnect the wire at
|