TM 5-4120-273-15
(2) Refer to figure 3-14 and remove the low
(2) Refer to figure 3-14 and remove the
pressure switch from the pressure switch mount-
high pressure switch from the pressure switch
ing box.
mounting box.
(3) Disconnect flare nut from low pressure
(3) Disconnect flare nut from high pressure
line connection and immediately cap to prevent
line connection and immediately cap to prevent
refrigerant loss.
refrigerant loss.
c. Installation.
c. Installation.
(1) Refer to figure 3-14 and install the low
(1) Refer to figure 3-14 and install the high
pressure switch.
pressure switch,
(2) Connect flare nut to low pressure con-
(2) Connect flare nut to high pressure con-
nection.
nection.
(3) Install top panel, condenser fan and fan
(3) Install top panel, condenser fan and fan
guard, refer to paragraph 3-18 and 3-20.
guard, refer to paragraph 3-18 and 3-20.
a. General. The fan speed switch changes the
a. General. The low pressure switch prevents
speed of the fan motor from low to high when the
the compressor from operating if the suction
pressure reaches 410 psig.
pressure drops below 25 psig.
b. Removal.
fan speed pressure switch.
(1) Remove top panel, condenser fan guard,
fan speed pressure switch.
condenser fan, refer to paragraph 3-18 and 3-20.
Section IV. LIQUID LINE SOLENOID VALVE AND EQUALIZER
SOLENOID VALVE
valve before reassembling valve to avoid heat
a. General. The liquid line solenoid shuts off
distortion (fig. 6-1).
the flow of refrigerant to the evaporator coil when
the thermostat is satisfied.
b. Removal. Slowly discharge refrigerant from
a. General. The equalizer solenoid valve is
actuated by the on-off switch and serves to equal-
move solenoid valves.
ize system pressures during shutdown.
b. Removal Slowly discharge refrigerant from
system (para 5-21c). Refer to figures 3-11, 3-12
solenoid valves.
and remove equalizer solenoid valve,
Caution: The solenoid valves must be dis-
c. Installation. Refer to figures 3-11, 3-12 and
assembled before disconnecting the tubing from
install equalizer solenoid valve. Evacuate and re-
the valve to avoid heat distortion. Refer to fig-
charge the refrigerant system (para 5-21c and 5-
ure 6-1.
21d).
|