(4) Loosen setscrews in condenser fan and remove fan (figure 4).
(5) Remove condenser mounting screws (figure 4).
(6) Disconnect tubes from condenser coil (para 75).
(7) Lift the condenser coil from the unit.
b.
Cleaning and Inspection.
(1) Clean the condenser coil by directing low pressure compressed
air through the fins.
(2) Inspect the condenser coil for leaks or damage.
(3) Repair or replace a leaking or damaged condenser coil.
c. Installation.
(1) Place the condenser coil in the unit and secure with all
mounting screws.
(2) Connect tubes to the condenser coil.
(3) Install condenser fan or motor shaft and tighten setscrews.
(4) Install condenser fan housing and secure with mounting screw
(5) Leak test, evacuate, and charge refrigerant system (para 74).
(6) Install top, left, right, and rear panels (para 39).
79. Receiver
a. Removal.
(1) Remove top, left -side, and rear panels (para 39).
(2) Release refrigerant charge (para 74).
(3) Disconnect tubes from. receiver (para 75).
(4) Remove nut from the bottom of unit (figure 5).
(5) Remove the receiver from the unit.
Cleaning and Inspection.
b.
(1) Clean the receiver with solvent and dry thoroughly.
|