| |
is defective and should be replaced. Check voltage
between terminals C2 of armature relay (K4)
and ground (El), terminal A2 of armature relay
K5 and ground (El), and terminal B2 of armature
relay (K5) and ground (El). 120 (±10) vac
should be indicated, or relay is defective and
should be replaced.
Warning: Be careful when working
with high voltage. Failure to comply can result
in serious injury or death.
(3) Removal.
(a) Refer to figure 3-4 and remove the
lower front access cover.
(b) Remove cover from junction box (fig.
3-10).
(c) Refer to figure 3-13 and remove the
relay.
(4) Installation. Installation is the reverse
of removal.
c. Compressor Start Relay.
(1) General. The compressor start relay op-
erates in conjunction with the time delay relay
(K3) and the high- and low-pressure cutout
switches (S6 and S7) to insure proper starting
sequence of the refrigerant compressor when ei-
ther S6 or S7 require non-operation.
(2) Testing.
(a) Apply 208 volts, 60 Hertz, 3-phase, ac
electrical power to the air conditioner.
(b) Place rotary switch (S1) in COOL po-
sition.
(c) Check voltage between terminals X1
and X2 of compressor start relay (K1). 30 vdc
(±3) vdc should be indicated. If 30 vdc is indi-
cated, and high-pressure cutout switch (S6),
low-pressure cutout switch (S7) and time delay
relay (K3) are in operating condition, proceed to
check voltage between terminals A2 and B2, B2
and C2, and C2 and A2. If 208 vac is not indi-
cated, compressor relay is defective and must be
replaced. If 30 vdc is not indicated between ter-
minals X1 and X2 of relay (K1), check for phase
ABC at phase sequence relay (K6) using a phase
meter. If phasing is incorrect, check unit incom-
ing power. If phasing is correct, check terminal 2
of relay (K6) for 110 vat. If 110 vac is not indi-
cated, relay is defective and should be replaced.
If 110 vac is indicated, check terminal 2 of XF1
for 110 vat. If 110 vac is not indicated; replace
fuse. Check for 110 vac at terminal 3 of XF1. If
110 is not indicated, replace fuse. If 110 vac is in-
dicated at terminals 2 and 3 of XF1, check for 30
vac at terminals X1 and X2 of transformer (T1).
If 30 vac is not indicated, transformer is defec-
tive and should be replaced. If 30 vac is indicated,
check terminals 2 and 3 of rectifier (CRI) for 30
vdc. If 30 vdc is not indicated, rectifier is defec-
tive and should be replaced. If 30 vdc is indicated,
check terminal 2 of XF2 for 30 vdc. If 30 vdc is
not indicated, replace fuse. If 30 vdc is indicated,
check terminal 1 of TB2 for 30 vdc (rotary
switch must be in COOL). If 30 vdc is not indi-
cated, replace rotary switch (S1). If 30 vdc is in-
dicated, check terminal 2 of low-pressure cutout
switch (S7) for 30 vdc. If 30 vdc is not indicated,
reset switch (S7) and recheck for 30 vdc. If 30
vdc is not indicated, replace low-pressure cutout
switch (S7). If 30 vdc is indicated, check termi-
nal 2 of high-pressure cutout switch (S6) for 30
vdc. If 30 vdc is not indicated, reset switch (S6)
and recheck for 30 vdc. If 30 vdc is indicated,
check terminal 3 of TB2 for 30 vdc. If 30 vdc is
not indicated, remove plug (P4) and check resist-
ance between pins D and E of connector (J4). If
no resistance, replace compressor. If resistance is
indicated, replace connector (J4). If 30 vdc is
indicated at terminal 3 of TB2, check terminals
5 and 7 of time delay relay (K3) for 30 vdc. If 30
vdc is not indicated at terminal 7 of K3, replace
relay (K3).
(3) Removal.
(a) Refer to figure 3-4 and remove the
lower f rent access cover.
(b) Remove from junction box (fig. 3-10).
(c) Refer to figure 3-13 and remove the
relay.
(4) Installation. Installation is the reverse
of removal.
d. Heater Relay.
(1) General The heater relay (K2) closes to
supply power to the electric heaters as called for
by the KI-HEAT or LO-HEAT setting of the ro-
tary selector switch (S2).
(2) Testing.
(a) Place rotary switch (S1) in LO-
HEAT position.
(b) Apply 208 volts, 60 Hertz, 3-phase, ac
electrical power to the air conditioner.
(c) Check voltage between terminals Xl
and X2 of heater relay (K2). 30 vdc should be in-
dicated. If 30 vdc is indicated between terminals
X 1 and X2, proceed to check voltage between ter-
minals Al and B1, B1 and C1, and C1 and A1. If
30 vdc is not indicated, heater relay is defective
and must be replaced. If 30 (±3) vdc is not indi-
cated, check for 30 vdc to ground (El) at termi-
nal 2 of thermostat (S2). If 30 vdc is not indi-
cated at terminal 2 of thermostat (S2), check for
phase ABC at phase sequence relay (K6), using a
phase meter. If phasing is incorrect, check unit
incoming power. If phasing is correct, check ter-
minal 2 of relay (K6) for 110 vat. If 110 vac is in-
3-19
|