TM 5-4120-341-13
D I R E C T SUPPORT TROUBLESHOOTING
Section II.
5-5. GENERAL
a. This section provides information useful in diagnosing and correcting unsatisfactory operation or
failure of the air conditioner. Each malfunction is followed by a list of probable causes and actions to take
to remedy the malfunction. You should perform the tests/inspections and corrective actions in the order
listed.
b. This manual cannot list all malfunctions that may occur; nor all tests or inspections and corrective
actions. If a malfunction is not listed or is not corrected by listed corrective actions, notify your supervisor.
Malfunction
Test or Inspection
Corrective Action
COMPRESSOR
1. COMPRESSOR WILL NOT START
Step 1.
Check compressor for proper operation and damage.
Replace defective compressor (para. 5-9).
2. COMPRESSOR CYCLES INTERMITTENTLY
Step 1.
Inspect sight glass for proper amount of refrigerant.
Add refrigerant as required (para. 5-8).
Step 2.
Check for high discharge pressure.
Discharge refrigerant from system (para. 5-8).
Step 3.
Check for air in refrigerant system,
Purge refrigerant system (para. 5-8).
AIR CONDITIONER
1. HIGH DISCHARGE PRESSURE
Step 1.
Check for excessive refrigerant in s stem.
Discharge refrigerant from system 1'
Step 2.
Check for air in refrigerant system.
Purge refrigerant system (para. 5-8).
2. LOW DISCHARGE PRESSURE
Step 1.
Check to see if compressor is pumping,
Replace defective compressor (para. 5-9).
Inspect sight glass for proper amount of refrigerant.
Step 2.
Add refrigerant as required (para. 5-8).
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |