TM 5-4120-341-13
TO 35E9-256-1
ACTION
REMARKS
LOCATION/lTEM
TOP OF HOUSING
Avoid bodily contact with liquid refrigerant and avoid inhaling refrigerant gas. Be
especially careful that Refrigerant 12 does not come in contact with eyes. In case of
refrigerant leaks, ventilate area immediately.
NOTE
Whenever available, use recycled refrigerant for charging the refrigeration sys-
q
tem.
The following steps a. through L, apply only to a completely evacuated system. To
q
add additional refrigerant to a charged system, refer to steps f. through j.
Remove valve cap from suction discharge valve.
a.
8. Charging Refrigerant System
Place inverted refrigerant drum on scale and note
b.
weight of drum.
Loosely connect the charging line of refrigerant
c.
drum to suction discharge valve.
Partially open refrigerant drum valve and purge air
d.
from charging line.
e.
Close refrigerant drum valve and tighten connec-
tion at suction discharge valve.
CAUTION
DO NOT operate air conditioner while charging the refrigerant system.
f.
Open suction discharge valve.
Open refrigerant drum valve and charge refriger-
9.
ant system until system and drum pressures are
equal or until 3.5 pounds of refrigerant have
entered the system.
|