|
|
TM 5-4120-352-14
(1) Wipe off all loose dirt with a dry cloth.
b. The control should be adjusted for the center
(2) Inspect push-pull control for smooth oper-
position between open and closed. The actuator
ation of core in casing. Inspect vent damper for bent
should then be in the centered position and the rod
or broken condition. Replace defective parts. In-
on top of the damper should be parallel with front of
spect for loose or damaged rubber seal on damper.
the housing.
Cement loose rubber or replace rubber if damaged.
c. Check operation. The control should move
Inspec actuator for bent condition. Straighten actu-
smoothly between the open and closed position.
ator or replace as required.
4-28. Removal.
4-30. Installation.
move the housing covers. Refer to figure 4-8 and re-
move vent damper as follows:
and install actuator, screw, two spring washers and
nut.
(1) Loosen screw on mechanical post and dis-
connect push-pull control.
vent damper in opening in housing. Secure cent
damper cover to housing with two screws and lock-
lift vent damper from air conditioner.
washers.
remove evaporator louvers. Refer to figures 4-7 and
8 and install control as follows:
(1) With one nut on each end of outer casing
(1) Remove screw, washer, nut, spacer, and
loop clamp.
of push-pull control, install ends of control through
opening in housing. Install outer nuts and insert
(2) Loosen screw on mechanical post to free
ends of wire core into mechanical post of damper
end of control wire core.
and actuator. Tighten outer nuts on casing.
(3) Remove outer nuts from both ends of con-
(2) Install clamp, spacer, screw, nut, and
trol outer casing and remove push-pull control.
washer.
and remove screw, nut, two spring washers and
control.
actuator.
ers.
4 - 2 9 . Cleaning, Inspection and Repair.
Clean, inspect and repair vent damper and con-
inlet and outlet louvers.
trol as follows:
Section XI. MAINTENANCE OF ELECTRICAL SYSTEM
4 - 3 2 . Testing and Inspecting the Elec-
4-31. General.
The electrical system consists of the evaporator
trical System.
Troubleshooting procedures for testing the elec-
and condenser fan motors, electric heaters and
trical system to isolate cause of trouble are covered
heater thermostatic switch, junction box, control
in paragraph 4-12. Additional detailed test infor-
module, transformer, rectifier, condenser fan motor,
mation is contained in specific paragraphs covering
high- low speed thermostatic switch and connecting
harnesses and wiring. Electrical assemblies and
the electrical components. Use a continuity tester
groups of associated components are covered in sep-
or multimeter set on low ohms to test for continuity.
Use an insulation tester or multimeter set on
arate sections.
higher ohm range to test for grounds between the
circuit in a component and the outside case of the
component. When testing an electrical component,
Disconnect air conditioner power
supply before performing mainte-
check also for visual damage and inspect all wiring
nance work on electrical system.
in the area for damage or loose connections.
4-20
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |