TM 5-4120-352-14
c. Fan Motor Thermal Protector Replace-
(5) Remove motor and mounting plate from
ment.
air conditioner.
(1) General. Organizational repair of motors
is limited to testing and replacement of defective
(1) and collar (2) from motor shaft. Remove four cap
thermal protectors. Instructions contained in this
screws (3), lockwashers (4) and flat washers (5). Re-
paragraph cover replacement of the motor thermal
move motor (6) and four flat washers (7) from
mounting plate (9). Remove bushings (8) from plate
only if they require replacement.
tially remove thermal protector housing from motor
by removing two screws and washers. Tag and dis-
connect electrical leads. Remove thermal protector.
Remove other protector in the same manner.
terminals. Replace protector if open.
(4) Installation. Install thermal protector in
housing and connect leads. Install thermal protec-
tor housing on motor and secure with screws and
washers previously removed.
Figure 4-13. Connector fan motor and mounting plate, ex-
ploded view.
4-29
|