Click here to make tpub.com your Home Page

Page Title: Section III. Repair Parts, Special Tools, and Equipment
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-4120-355-14
Section III. Repair Parts, Special Tools, and Equipment
4-8. Special TOOIS and Equipment
No special tools or equipment are required.
Repair Parts
4-9.
Repair parts are listed and illustrated in the repair parts and special tools list, TM5-4120-355-24P, covering organi-
zational maintenance for the air conditioner.
Section IV. Lubrication Instructions
No lubrication is required.
Section V. preventive Maintenance Checks and services (PMCS) (QUART)
4-10. General
The necessary preventive maintenance services to be performed are listed and described in table 4-1. The sequence
numbers indicate the minimum inspection requirements. Defects discovered during operation of the unit will be noted
for further correction, to be made as soon as operation has ceased. Stop operation immediately if a deficiency is noted
during operation which would damage the equipment if operation were continued. All deficiencies and shortcomings
will be recorded together with corrective action taken on DA Form 2404 (Equipment inspection and Maintenance Work-
sheet) at the earliest possible opportunity.
4-11. Quarterly Preventive Maintenance
Table 4-1 contains a tabular listing of preventive maintenance services which must be performed by organizational
maintenance personnel. The sequence numbers are listed consecutively and indicate the minimum requirements.
O r g a n i z a t i o n a l Preventive Maintenance Checks and Services
Q-Quarterly
Item
Interval
Item to be
No.
Inspected
Procedures
Q
Air
Filter
1
Clean and service as required.
2
Clean and service as required.
Coil
3
C o n d e n s e r Coil
Clean and service as required.
4
Fan Motor
Clean and service as required. Turn shaft to be
sure bearings are not defective.
Air Condi-
5
Lubricate all movable connections and linkage with
tioner  Unit
SAE 30 oil.
C h e c k for loose, missing, or damaged
components.
Clean and service as required.
6
S i g h t Glass
Check for damaged or broken glass. Check for full
condition of unit.
7
Wiring
Look for broken or loose wires on connections.
8
Inspect refrigerant hoses and tubing for signs of
Refrigerant
leakage  abrasion,  tearing,  kinking,  etc.

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business