TM 5-4120-356-14
TABLE B
TABLE A
TABLE C
TABLE D
TEST PROCEDURES FOR RELAYS K4 AND K5
1.
WITH RELAY DE-ENERGIZED, CHECK FOR CONTINUITY BETWEEN TERMINALS SHOWN IN TABLE A. REPLACE
RELAY IF ANY OPEN CIRCUIT IS FOUND.
2. WITH RELAY DE-ENERGIZED, CHECK FOR SHORT CIRCUIT BETWEEN TERMINALS SHOWN IN TABLE B. REPLACE
RELAY IF ANY SHORT CIRCUIT IS FOUND.
3.
4. WITH RELAY ENERGIZED, CHECK FOR CONTINUITY BETWEEN TERMINALS SHOWN IN TABLE C. REPLACE RELAY
IF ANY OPEN CIRCUIT IS FOUND.
5. WITH RELAY ENERGIZED, CHECK FOR SHORT CIRCUIT BETWEEN TERMINALS SHOWN IN TABLE D. REPLACE
RELAY IF ANY SHORT CIRCUIT IS FOUND.
TS54120-35614/3-17
6.
DE-ENERGIZE RELAY.
F i g u r e 3-17. Test procedures for fan relays K4 and K5
|