(c) Purge the refrigerant system in accordance with the procedures given in paragraph 48.
(d) Check the condenser coil and the dehydrator for leaks in accordance with the procedures given in
paragraph 4-4c. Repair any leaks found in accordance with paragraph 4-4d.
(e) Refer to figure 4-4 and evacuate the refrigerant system.
(f) Refer to figure 4- 10 and charge the system with refrigerant.
(g) Install the condenser fan (paragraph 3-15b).
m. Evaporator Coil.
(1) Inspection.
(a) Turn the selector switch to the "OFF" position and disconnect the air conditioner from the electri-
cal power source.
(b) Inspect the evaporator coil for damage or defects which would impair serviceability.
(c) Check the evaporator coil for leaks in accordance with the procedures given in paragraph 4-4c.
Repair any leaks found in accordance with paragraph 4-4d.
(d) Check evaporator output by comparing the dry bulb temperatures of air entering and leaving the
evaporator; the temperature difference should be 18-22F across the evaporator.
(2) Replace. Replace the evaporator coil if evidence is found of defects or damage which would impair
serviceability or if unrepairable leaks or damage is found. Refer to steps (3) and (4) for removal and installa-
tion of evaporator coil.
(3) Removal.
(a) Refer to figure 4-2 and release refrigerant from the system
(b) Refer to figure 3-27 and remove heater elements HRl, HR2 and HR3 to gain access to the evapora-
tor coil.
(c) Refer to figure 4-21 and remove the evaporator coil.
(4) Installation.
(a) Refer to figure 4-21 and install the evaporator coil.
(b) Perform any further maintenance of refrigerant components which may be required.
(c) Purge the refrigerant system in accordance with the procedures given in paragraph 48.
(d) Refer to paragraph 4-4c and check the evaporator coil and dehydrator for refrigerant leaks. If any
leaks are found, repair them in accordance with the procedure given in paragraph 4-4d.
(e) Refer to figure 4-4 and evacuate the refrigerant system.