4120-01-069-1321)">
|
|
TM 5-4120-359-14
Table 4-4. NORMAL OPERATING PRESSURES
Temperatures
Pressure Range (psig)
Outdoor ambient
50F (10C)
75F (24C)
100F (38C)
120F (49C)
90F(32C) Return
55-65
59-70
60-75
75-90
Air to Unit
Suction
Suction
Suction
Suction
(Dry Bulb)
125-160
175-210
255-295
370-410
Discharge
Discharge
Discharge
Discharge
80F (27C) Return
58-65
58-70
60-75
65-75
Air to Unit
Suction
Suction
Suction
Suction
(Dry Bulb)
120-155
170205
250-290
370-410
Discharge
Discharge
Discharge
Discharge
4-12. FINISH REPAINTING AND REFINISHING GENERAL
Tools: Refer to SB 11-573, painting and preservation supplies available for field use for electronics command equipment.
Supplies: Yellow primer MIL-P-52192 or TT-P-1757 (item 9, Appendix E) Forest Green enamel, MIL-E-52798 (item 10,
a. Touch up and repaint in accordance with TB 746-10, field instructions, for painting and preserving electronics
command equipment.
b. Care for painting equipment in accordance with TM 9-213, painting instructions for field use.
4-37
|