4-32. HEATING ELEMENTS, (HR1 THROUGH HR15) INSULATING GROMMET AND BRACKET
Preliminary Procedure: Remove fan and motor assembly. (See paragraph 4-21.)
WARNING
Allow electrical heating elements to cool before touching. Severe burns can result
from touching hot heaters.
Figure 4-29. Heater Assembly - Model DHF
a. Removal (See Figure 4-30.1 for models EKP and FGG)
(1) Using screwdriver, tag and disconnect heater leads from terminal board TB-2.
(2) Using screwdriver, remove the four screws from the mounting bracket flanges.
(3) Carefully lift the heater assembly up and out of the unit.
4-74 Change 5