d. Installation - Model DHF
(1) Position cylinder and insert mounting studs through bracket.
(2) Using wrench, secure cylinder to bracket with two lock nuts.
(3) Using wrench, connect and tighten flare nut.
(4) Using screwdriver and wrench, secure the two push-pull control wire ends to the actuator rod with two screws
and lock nuts.
(5) Replace the dehydrator. (See paragraph 4-73.)
(6) Leak test all new connected joints and those in the repair area. (See paragraph 4-8.)
(7) Evacuate and charge the refrigerant system. (See paragraphs 4-9 and 4-10.)
e. Installation - Models EKP and FGG
(1) Position cylinder and insert mounting studs through bracket.
(2) Using wrench and screwdriver, secure cylinder to bracket with two lock nuts and screw.
(3) Using wrench, connect and tighten flare nut.
(4) Using screwdriver and wrench, secure the two push-pull control wire ends to the actuator rod with two screws
and lock nuts.
(5) Replace the dehydrator. (See paragraph 4-73.)
(6) Leak test all newly connected joints and those in the repair area. (See paragraph 4-8.)
(7) Evacuate and charge the refrigerant system. (See paragraphs 4-9 and 4-10.)
Follow-on Procedures: 1. Install top condenser cover. (See paragraph 3-25.)
2. Connect power.
4-76. ACTUATOR BRACKET
Preliminary Procedures:
1. Disconnect power.
2. Remove air conditioner from shelter (if required). (See paragraph 3-6).
3. Remove top condenser over. (See paragraph 3-25.)
4. Remove light end condenser cover. (See paragraph 3-26.)
a. Inspect
(1) Check that bracket is not cracked , broken , or otherwise damaged. Replace if damaged.
(2) Check that plate nuts are not loose, broken, or missing. Replace them if they are missing or broken.