| |
Figure 5-4.
TM 5-4120-361-14
(7) Refer to figure 6-1 and purge
cardiac rhythm abnormalities
the refrigerant system.
or the induction of arryth-
mias, as a result of exposure
(8) Refer to figure 6-2 and charge
to fluorocarbon refrigerant
the refrigerant system.
gases (freons).
Such indivi-
duals should be evaluated by
local medical authorities be-
5-19.
Condenser Coil.
fore working in environments
where potential freon exposure
a. Removal.
Remove condenser coil
may occur.
as follows:
1.
Caution should be exer-
cised with fluorocarbon re-
frigerant gas (freons) as they
can displace oxygen and there-
by cause suffocation.
2.
Personnel with a history
or other evidence of cardiac
rhythm abnormalities should be
made aware of the potential
for aggravation of existing
(1) Refer to figure 6-1 and dis-
charge the refrigerant system.
(2) Refer to figure 4-4 and remove
housing top covers.
(3) Refer to figure 4-3 and remove
condenser guard.
(4) Refer to figure 4-9 and remove
power actuator, bracket and left con-
denser fan motor and supports.
(5) Disconnect tubing from con-
denser coil and remove other tubing and
fittings as required.
5-11
|