| |
Figure 5-5.
TM 5-4120-361-14
(1) Reinstall push-pull control as-
sembly brackets on replacement cylin-
der.
(2) Install actuator cylinder (fig-
ure 5-5) with studs through openings in
bracket.
Install lockwashers and nuts
on studs.
(3) Connect flare nut.
(4) Install push-pull control.
Place outer control casing clips over
wire and insert wire ends into openings
in mechanical posts on louver lever and
actuator cylinders.
(5) Install push-pull control clips
to hold control in position.
Install
loop clamp, screw, and lockwashers.
(6) Adjust control as described in
c. below.
c. Adjustment. Before system is
charged, adjust louver push-pull control
as follows:
(1) Close louver blades and tighten
screw in mechanical post to lock wire on
that end.
(2) Extend actuator rod until there
is a 1/4 inch space between inner edge
of mechanical post bracket and the
face of the cylinder.
Tighten the mech-
anical post screw.
(3) Refer to figure 4-4 and in-
stall housing top covers.
1.
Caution should be exer-
cised with fluorocarbon re-
frigerant gas (freons) as they
can displace oxygen and
thereby cause suffocation.
2.
Personnel with a history
or other evidence of cardiac
rhythm abnormalities should be
made aware of the potential
for aggravation of existing
cardiac rhythm abnormalities
or the induction of arryth-
mias, as a result of exposure
to fluorocarbon refrigerant
gases (freons).
Such indivi-
duals should be evaluated by
local medical authorities be-
fore working in environments
where potential freon exposure
may occur.
(4) Refer to figure 6-2 and charge
the refrigerant system.
5-13
|