Click here to make tpub.com your Home Page

Page Title: PERFORMANCE DATA.
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-4120-369-14
when required, from the outside of the unit, through the fresh air filter and ventilation duct; air
is then forced over the heater elements through evaporator coil, mist eliminator and outlet louver.
The outlet louver has adjustable blades for directing the air flow into a desirable pattern within
the space being conditioned.  The evaporator fan speed is controlled by a toggle switch on the
control module.
Condenser Section.  The condenser section (figure 1-2 ) located in the rear part of the
b.
air conditioner contains the condenser coil, condenser coil guard, two condenser motors and fans,
motor compressor, condensor, condensor fan housings and louvers, louver actuator, ventilation
air duct, fresh air filter and vent screen, thermal switch, refrigerant liquid sight indicator,
solenoid valves, expansion valve, pressure relief valve, system access service valves, filter drier,
refrigerant liquid receiver, accumulator, associated electrical wiring and refrigerant tubing and
an alternate power input connector.  The condenser fan speed controlled by a thermal switch
located on the rear of unit.  At ambient temperatures of 100F  5F (38C 3C) or higher, the
condenser fan motors will operate at high speed (3750 RPM); and at ambient temperatures below
100F (38C) , the motor will operate at low speed (1800 RPM).  Due to possible thermal lag, the
change over may be slow to react when the ambient temperature drops below the 100F (38C)
changeover point.
DIFFERENCE BETWEEN MODELS.
Difference data sheets are not applicable to this manual.
PERFORMANCE DATA.
The following listing contains the performance and dimensional
data applicable to the air conditioner.
(1) Air conditioner, model MIL-AC-1832
Air conditioner, horizontal, compact
Nomenclature . . . . .
Crippen and Graen
Manufacturer . . . . .
Model No. MIL-AC-1832
Capacity:
18,000 BTUH
Cooling . . . . . .
14,300 BTUH
High . . . . . .
7,500 BTUH
Low . . . . . .
590 scfm
Ventilation . . . .
3
Phase  .  .  .  .  .  .  .
Hertz . . . . . . . .
50/60
208
AC Volts . . . . . . .
Current input, full load, amperes
26.4
Coding . . . . . .
15
High heat . . . . . .
15
Low heat . . . . . .
15
Ventilating . . . . .
R22
Refrigerant . . . . . .
Amount of charge, pounds
4 lbs (1.816 kg)
(2) Dimensions and weights:
30.0 in. (72.4 cm)
Length
...
.
.
.
..
20.0 in. (48.3 cm)
Height
...
.
.
.
..
27.9 in. (67.3 cm)
Width
...
.
.
.
..
265 lbs
Weight
...
.
.
.
.
Section III.
TECHNICAL PRINCIPLES OF OPERATION
REFRIGERATION CYCLE.
The Refrigerant Cycle.  The refrigeration system removes heat from a given area. See
a.
Figure 1-3 for a schematic of the refrigeration cycle.

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business