TM 5-4120-369-14
d.
Connections.
(1) Conned to earth ground (see Figure 2-5) as follows:
Step 1.
Clean front of ground connection to obtain a bright metal surface.
Remove insulation from ends of grounding wire or use bare ends. Make
Step 2.
loop at wire ends.
Step 3.
Using 1/4-20 screw and washer, attach one end of wire to air conditioner
front panel ground connection.
Wrap a suitable length of perforated strap around clean surface on water
Step 4.
pipe or grounding rod. Do not use gas pipe.
Using 1/4-20 screw, two washers and nut, attach other end of grounding
Step 5.
wire to strap in a manner such as to securely tighten strap to pips and
wire to strap.
Ground wire installation