TM 5-4120-369-14
Troubleshooting - Continued
Table 4-2.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
AIR CONDITIONER FAILS TO OPERATE - Continued
Step 4.
Check to see if mode selector rotary switch is improperly positioned or
is defective.
Turn selector to COOL or VENT.
Replace switch if defective
Step 5.
Check to see if control circuit breaker or compressor circuit breaker is
in OFF position or is defective.
Reset circuit breaker(s) or replace defective circuit breaker (paragraph 4-26).
Step 6.
Check to see if high pressure or low pressure switch has cutout.
Reset high pressure or low pressure cutout. Note that time delay
relay starts compressor 30 seconds after reset.
Test control circuit transformer and rectifier for faulty
Step 7.
operation.
Replace defective transformer and/or rectifier (paragraph 4-28 and 4-29).
2.
INSUFFICIENT COOLING
Check to see if the mode selector switch is improperly positioned.
Step 1.
Set switch to COOL.
Step 2.
Check to see if temperature selector control is inproperly positioned or
is defective.
Adjust setting or replace switch (paragraph 4-26).
Step 3.
Check to see if fresh air damper control is incorrectly set or
improperly adjusted.
Verify setting and, if neceesary, correct adjustment of damper
control (paragraph 4-39).
Step 4.
Check to see if evaporator outlet louver is bent or stuck in closed position.
Repair or replace louver. (paragraph 4-7)
Step 5.
Inspect condenser coil for dirt accumulation.
Clean coil (paragraph 4-5).
Step 6.
Inspect evaporator return air filter for dirt accumulation.
Clean filter (paragraph 4-3).
Step 7.
Check to see if evaporator fan is loose or defective.
Tighten if loose or replace if defective (paragraph 4-21).