TM 5-4120-369-14
TROUBLESHOOTING
Section VI.
GENERAL.
4-13.
This section contains troubleshooting instructions for the isolation of causes and common
troubles that may occur during operation, and also gives the possible remedies to correct the
trouble.
ORGANIZATIONAL TROUBLESHOOTING CHART.
General.  Troubleshooting procedures for organizational maintenance personnel are listed
a.
in table 4-2. As shown in the table, troubleshooting begins by identifying the malfunction.  Next,
suitable tests of inspections are made in step-by-step order.  Finally, a corrective action is given.
Remedies beyond the scope of organizational maintenance must be given in paragraph (b) and (c)
which follow :
Control Circuit.  The cause for the failure of the system to operate can be narrowed
b.
to a specific portion of the system if the control component associated with the failure can be
isolated.  It is the purpose of safety devices to open the circuit under certain overload or
fault conditions.  If a safety device is open, additional check is required to determine if the
open is due to faulty safety device or if the safety device is performing its intended function,
and the fault is located else where in the system.  To check the control circuit, proceed as
follows:
(1) Disconnect air conditioner from source of power.
(2) Using a series test lamp or ohmmeter, check the continuity through each control
in the affected circuit with the control in the closed position while being checked.  Use the
system schematic and wiring diagram for point-to-point circuit tracing.
(3) Replace each defective part with a serviceable like item.
Safety Devices.  When testing the control circuit and associated components, take into
c.
account the normal state of the safety device. Determine (1) whether it is normal for the device
to be open under the existing conditions or (2) if the open condition indicates trouble else where
in the air conditioner.
Troubleshooting
NOTE
Before you use this table, be sure you have performed all applicable operating checks.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
AIR CONDITIONER FAILS TO OPERATE
1.
Step 1.
Check to see if main power cable is connected.
Connect cable to power source.
Check to see if main power receptacle is defective.
Step 2.
Replace defective connector. (Paragraph 4-16.)
Check for loose electrical connections.
Step 3.
Tighten loose connections.