4-30.
JUNCTION BOX COMPONENTS - Continued.
(5) Condenser Fan Relay (K-4).
Condenser Fan Relay
(a) T e s t i n g .  Check for loose connections and cracked or broken casing.
Check for continuity with a multimeter.  If no continuity exists or if the casing is cracked
or broken, replace the relay.
(b) Removal.
(1) Refer to paragraph 4-27 and remove the junction box.
(2) Refer to figure 4-18 and remove the condenser high speed relay.
(c) Installation.
(1) Refer to figure 4-16 and install the condenser high speed relay.
(2) Refer to paragraph 4-29 and install the junction box.