TM 5-4120-374-13
3-5. AIR DIFFUSER AND RETURN AIR GRILLS
This task covers:
c. Adjustment
a. Inspection
b. Service
I N I T I A L SETUP
Troubleshooting Reference
Material/Parts
AIR CONDITIONER, Malfunction 2, Step 3
Air Diffuser Grill
Approximate Time Required (in minutes)
Return Air Grill
Dry Cleaning Solvent, App. E, Items 2 & 3
15
Inspection and Service
Adjustment
5
References
None
T O T A L TIME
20
.
REMARKS
ACTION
LOCATION/lTEM
INSPECTION AND SERVICE
FRONT OF HOUSING
Dry cleaning solvent P-D-680 or P-S-661 used to clean parts is potentially
dangerous to personnel and property. Avoid repeated and prolonged skin contact.
Do not use near open flame or excessive heat. Flash point of solvent is 100F (38 C).
1. Air Diffuser Grill a. Brush off any loose dirt or foreign matter from air diffuser grill.
b. Wipe off air diffuser grill with a cloth moistened with dry cleaning
solvent, P-D-680 or P-S-661.
c. Inspect for and remove any obstructions.
d. Inspect air diffuser grill for security of attachment and damage.
e. Report damaged condition to organizational maintenance personnel.
2. Return Air Grill
a. Brush off any loose dirt or foreign matter from return air grill.
b. Wipe off return air grill with a cloth moistened with dry cleaning
solvent P-D-680 or P-S-661.
c . Inspect for and remove any obstructions.
d. Inspect return air grill for security of attachment and damage.
e. Report damaged condition to organizational maintenance personnel.
3. Return Air Control a. Adjust return air grill louvers by rotating return air control from
CLOSED to OPEN positions.
b. Verify return air grill louvers operate freely.
c. Report damaged condition to organizational maintenance personnel.
|