TM 5-4120-374-13
4-20. CONDENSER FAN (CONT)
LOCATION/lTEM
ACTION
REMARKS
FRONT OF HOUSING
3. Return Air Grill
a. Remove eight (8) screws securing return air grill.
b. Remove return air grill.
4. Air Diffuser Grill
a. Remove eight (8) screws securing air diffuser grill.
b. Remove air diffuser grill.
5. Control Panel Plate
a. Loosen setscrews and remove knobs from return air control,
selector switch and thermostat switch.
b. Remove two (2) screws securing control panel plate.
c. Remove control panel plate.
6. Front Panel
a. Remove two (2) screws securing thermostat switch to
front panel.
b. Remove fourteen (14) screws securing front panel.
c. Remove front panel.
7. Blower Intake Ring
a. Remove seven (7) screws securing blower intake ring.
b. Remove blower intake ring.
8. Circulating Fan
a. Loosen setscrew in hub of circulating fan.
b. Carefully remove circulating fan.
RIGHT SIDE OF HOUSING
a. Remove upper four (4) capscrews and self-locking nuts
9. Condenser Fan
securing fan motor to motor mounting bracket.
b. Slide fan motor back against bulkhead.
c. Loosen setscrew in hub of condenser fan.
d. Remove condenser fan.