5-8. COMPRESSOR (CONT)
REMARKS
ACTION
LOCATION/lTEM
TOP AND LEFT SIDE OF HOUSING
a. Install compressor through left side of housing.
8. Compressor
b. Align holes in compressor mounting feet with holes in housing.
c. Secure compressor with eight (8) flatwashers, four (4) cap-
screws and four (4) nuts.
d. Install two (2) refrigerant lines on compressor and tighten
flare nut on suction refrigerant line.
e. Refer to paragraph 5-7 and solder discharge refrigerant line.
TOP AND REAR OF HOUSING
a. Align holes in rear panel with holes in housing.
9. Rear Panel
b. Secure rear panel with fourteen (14) screws.
a. Align holes in top rear panel with holes in housing.
10. Top Rear Panel
b. Secure top rear panel with nine (9) screws.
11. Refrigerant System Refer to paragraph 5-7 and charge refrigerant system. Refer to
burnout procedure if a burnout has been detected.
a. Align holes in top center panel with holes in top rear panel
12. Top Center Panel
and top front panel.
b. Secure top center panel with ten (10) screws.