Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-4120-374-13
5-11. CONDENSER COIL (CONT)
ACTION
REMARKS
LOCATION/lTEM
H O U S I N G INTERIOR
7. Condenser Coil
a.
Check all condenser coil tubing and sweat fittings with a
General Electric Type H-2 Halogen Test Detector (or
approved equal).
b.  Calibrate the detector with a General EIectric LS-20
leak standard (or approved equal) for a pure refrigerant
leak rate of 0.1 ounce per year.
c.  Mark all spots where leaks are noticed.
d.  Repair leaks or replace condenser coil.
Purge system with dry nitrogen prior to soldering. Refrigerant heated
to 1200F creates phosgene gas.
a. Repair minor leaks or holes by soldering.
8. Condenser Coil
b. Use a silver solder with a 50% silver capacity and a melting
point of approximately 1160F (634.8C).
c. Straighten bent fins prior to installation.
5-30