TM5-4120-376-14
4-23. AMIBENT THERMOSTAT AUXILIARY POWER INLET/Inspect, Test, Repair, Replace
(Cont)
LOCATION/ITEM
Removal:
3. Remove fourteen screws (7) and front cover (8) from housing.
4. Remove seven screws (9) and center cover (6) from housing.
5. Remove condenser fans, motor and support assembly in accordance with paragraph 4-15,
page 4-43.
6. Remove two clamps (10) two screws (11) and two lock washers (12) and auxiliary inlet
power connector assembly (13) from housing.
7. Remove four screws (14) four flat washers (15) and four lock nuts (16) and inlet power
connector assembly, dust cover (17) and gasket (18) from housing.
8. Disconnect connector (J-12) (19) from bulkhead.
9. Remove inlet power connector assembly (J-12).
4-133
|