TM5-4120-376-14
4-26. HOUSING ASSEMBLY/Repair, Replace (Cont)
LOCATION/ITEM
Installation:
1. Align condenser louver assembly (21) with holes in condenser fan
four screws (20).
2. Align inlet ring (venturi) (19) with holes in condenser fan housing
screws (17) and four flat washers (18).
housing and secure with
and secure with four
3. Align condenser fan housing assembly with holes in bulkhead and housing and secure with
two screws (15) and two lock washers (16).
4. Secure condenser fan housing
assembly with thirteen screws (12)
and thirteen lock washers (13).
5. Install condenser coil in
accordance with paragraph 5-23,
page 5-76.
6. Install condenser fan motor
support in accordance with para-
graph 5-17, page 5-22.
7. Install condenser fans, and
support assemblies in accordance
with paragraph 4-15, page 4-46.
8. Install condenser louver
cable actuator in accordance with
paragraph 5-18, page 5-29.
9. Align condenser coil guard
(11) with holes in housing and secure
condenser coil guard to housing with
eighteen screws (10).
10. Align front louver
(evaporator inlet) (9) with holes in
housing and secure with ten screws
(7) and ten lock washers (8).
11. Align rear cover (6) with holes
in center cover and housing and secure
rear cover in center cover and
housing with fourteen screws (5).
4-164
|