TM5-4120-376-14 Table  5-1.  DIRECT  SUPPORT  MAINTENANCE  TROUBLESHOOTING  (Cont) MALFUNCTION TEST  OR  INSPECTION CORRECTIVE  ACTION Step  2. a. b. Check   compressor   for   damaged   valves,   bleed   off   refrigerant   to   pressures   in accordance  with  Table  5-2. Test   compressor   in   accordance   with   paragraph   5-22,   page   5-64. Replace   compressor   in   accordance   with   paragraph   5-22,   page   5-67. Table  5-2.  NORMAL  TEMPERATURE-PRESSURE  RELATIONSHIPS 95°F  (36°C)  dry  bulb  return  air  to  unit Outdoor   ambient 50F 75F 100F 110F 125F temperature 10C 24C 38C 4.35C 52C GAUGE  PRESSURES Suction  (psig) 58-65 58-70 60-75 62-72 65-75 (Kg/Cm²,    4.1-4.6 4.1-4.9 4.2-5.3 4.4-5.1 4.6-5.3 Discharge   (psig) 120-155 170-205 250-290 300-390 370-410 (Kg/Cm²,    8.4-10.9 11.9-14.4 17.6-20.4 21.1-2.4 26.0-28.8 NOTE Dry  bulb  temperatures  are  measured  with  an  ordinary  thermometer. SECTION  III.  REFRIGERATION  SYSTEM  SERVICES 5-6.  INSTRUCTION.  This  section  contains  all  the  necessary  instructions  to  perform refrigeration   system   services.    For  your  convenience,  an  index  of  this  section  follows. 5-9

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business