TM5-4120-376-14
5-18. CONDENSER LOUVER ACTUATOR AND CONTROL ASSY/Service, Adjust, Replace
(Cont)
LOCATION/ITEM
LOUVER CONTROL CABLES
Adjustment:
1. Close louver blades.
2. Extend cable actuator (22) until there is 1/4 inches of space between inner edge of bracket
(23) and the face of the cable actuator (22).
3. Tighten screws (24) on bracket (23).
5-28
|