TM5-4120-376-14
5-18. CONDENSER LOUVER ACTUATOR AND CONTROL ASSY/Service, Adjust, Replace
(Cont)
LOCATION/ITEM
LOUVER CONTROL ACTUATOR
Installation:
1. Align cable actuator (10) with holes in mounting bracket (11) and secure with two flat nuts
(8) and two lock washers (9).
2. Align cable actuator and secure flare nut (7).
3. Test, evacuate and charge in accordance with paragraph 5-8 through 5-14, page 5-10
through 5-19.
4. Close louver blades (13).
5. Extend condenser cable actuator rod (14) until there is 1/4 inch of space between inner
edge of mounting bracket (15) and the face of the cable actuator (10).
6. Tighten screws (12).
5-29
|