TM5-4120-376-14
5-18. CONDENSER LOUVER ACTUATOR AND CONTROL ASSY/Service, Adjust, Replace
(Cont)
LOCATION/ITEM
LOUVER CONTROL CABLES
Installation:
5. Align cables (12) with connecting links (13) and secure with two screws (11).
6. Align cable housing (13) with discharge line (23) and secure with two clamps (10) two
screws (7) two lock washers (8) and two flat nuts (9).
7. Align control cables (12) with mounting bracket (19) and secure with two screws (14).
8. Adjust louver control cable in accordance with paragraph 4-25, page 4-153.
9. Align rear cover (4) with holes in center cover (6) and housing and secure with fourteen
screws (5).
10. Align fabric
washers 2).
cover (3) with holes in housing and secure with three screws (1) and three lock
5-31
|