TM5-4120-376-14
5-19. REFRIGERANT VALVES AND RELATED TUBING/Test, Repair, Replace (Cont)
LOCATION/ITEM
EXPANSION VALVE (THERMAL)
Removal:
5. Discharge the system in accordance with paragraph 5-8, page 5-10.
6. Remove mastic (Table D-1, Item 20) from bulb well (10).
7. Remove sensor bulb (11) from bulb well (10).
8. Remove one screw (12) one clamp (13) one lock washer (14) and one spacer (20) securing
cap line (15) to bulkhead.
9. Remove one screw (16) one clamp (17) and one spacer post (18) securing expansion valve
(19) to bulkhead.
10. Debraze expansion valve in accordance with paragraph 5-9, page 5-11.
5-34
|