TM5-4120-376-14 5-19.  REFRIGERANT  VALVES  AND  RELATED  TUBING/Test,  Repair,  Replace  (Cont) LOCATION/ITEM SOLENOID   VALVE   (L-1)   (L-2) Removal: 1.  Discharge  the  system  in  accordance  with  paragrph  5-8,  page  5-10. 2.   Disconnect   solenoid   valve   electrical   connector   P-8   (10). 3.   Remove   retaining   nut   (11)   nameplate   (12)   and   lift   coil   (13)   from   plunger   assembly   (14). 4.   Remove   two   screws   (15)   securing   plunger   assembly   (14)   to   solenoid   valve   base   (16). 5.   Remove   plunger   assembly   (14)   O-ring   (17)   and   diaphragm   (18). 6.  Remove  two  screws  (19)  securing  valve  base  (16)  to  bulkhead. 5-36