TM  5-4120-377-14 TABLE  4-2.  TROUBLESHOOTING  (Cont.) MALFUNCTION TEST  OR  INSPECTION CORRECTIVE  ACTION Step 3.  Check that the louvers in the conditioned air inlet and outlet grilles are properly adjusted. (Must be open.) Adjust  louvers  properly. Step  4.  Check  to  be  sure  that  excessive  hot,  outside  air  is  not  being  introduced  through  the  fresh  air damper. Fully  close  damper;  then,  if  condition  improves,  adjust  properly. Step 5.  Check  to  be  sure  condenser  air  inlet  and  outlet  are  not  obstructed. Remove  obstructions. 4-45