TM  5-4120-377-14 TABLE 4-2. TROUBLESHOOTING (Cont.) MALFUNCTION TEST  OR  INSPECTION CORRECTIVE  ACTION 6. REDUCED HEATING CAPACITY. Step 1.  Check  that  all  doors,  windows,  and  other  openings  in  the  room  or  enclosure  are  tightly  closed. Tightly  close  all  openings. Step 2.  If  control  panel  is  remotely  located,  check  to  be  sure  that  sensing  bulb  is  not  near  a  light  bulb  or some  type  of  heat  producing  equipment. Turn  off  or  move  heat  source,  or  move  the  remote  control  panel. Step 3.  Check   operation   of   Temperature   control   thermostat. Set  control  to  fully  INCREASE;  then,  if  condition  improves,  adjust  properly. TS4120-377-14M-T42-15 Step  4.  Check  that  the  louvers  in  the  conditioned  air  inlet  and  outlet  grilles  are  properly  adjusted. Adjust  louvers  properly. 4-47