TM5-4120-377-14
c. Cleaning
Preliminary procedure: Remove mist eliminator. (See para 4-35.)
(1) Pour some clean fresh water into condensate drip pan.
(2) If water does not flow out of the ends of the drain tubes or has a muddy appearance, insert a flexible
wire up the drain tube. Agitate until clog and accumulated debris are loose.
(3) Pour additional water in the drip pan until an unrestricted flow of clean water pours from the ends of
the drain tubes.
(4) Be sure the springs, balls, and ball seats (end of drains where balls and springs are inserted) are clean.
Follow-on procedure: Install mist eliminator. (See para 4-35.)
d. Installation
(1)
(2)
(3)
(4)
(5)
(6)
Insert balls and springs. Be sure that balls are above springs.
Depress springs with screwdriver far enough to install cotter pins.
Secure cotter pins.
Slip drain hoses up and in place on casing drain tubes.
Using screwdriver, secure clamps.
Secure (push in place) drain connection tubes in spring retainers on casing sides.
Follow-on procedure: Install junction box. (See para 4-46.)
4-124
|