c. Repair/Replacement. Should a leak or major damage be evident, refer to direct support maintenance.
Follow-on procedure: 1. Install
2. Install
3. Install
4-66. CONDENSATE TRAPS
condenser coil guard. (See para 4-26.)
junction box. (See para 4-46.)
radio frequency filter. (See para
Preliminary procedure: Remove junction box. (See para 4-46.)
a. Removal
4-44.)
Figure 4-79.
Condensate Drain Traps
(1)
(2)
(3)
(4)
Disengage drain connection tubes from spring retainers on casing sides.
Using screwdriver, loosen top hose clamps on drain hoses.
Slip hoses down and off of casing drain tubes.
Using pliers, remove cotter pins.
(5) Remove springs and balls from drain ends.
b. Inspection
(1) Check balls, springs, and cotter pins for nicks and wear.
(2) Replace balls if they are nicked or have any damage that would keep them from sealing properly.
(3) Replace springs if they are worn or have any damage that would keep them from applying pressure to
balls.
4-123
|