TM5-4120-383-14
EQUIPMENT DATA.
AMBIENT OPERATING
TEMPERATURE RANGE
-50F (-45C)
LOW
+120F (+49C)
HIGH
PERFORMANCE
10,000 BTU/HR
COOLING CAPACITY
HEATING CAPACITY
7,000 BTU/HR
POWER REQUIRED
208
VOLTAGE
PHASE
3
HERTZ
50/60
DIMENSIONS
24.0 inch (60.96
cm)
WIDTH
DEPTH
26.5 inch (67.31
cm)
HEIGHT
16.0 inch (40.64
cm)
WEIGHT
185 pounds (83.9
kg)
REFRIGERANT
R-22
TYPE
CHARGE
2.2 pounds (1.0 kg)
Section III
TECHNICAL PRINCIPLES OF OPERATION
REFRIGERATION CYCLE.
(See fig. 1-3.)
a.
Cooling Cycle.
q The COMPRESSOR (1) takes cold, low pressure refrigerant gas
and compresses it to a high temperature, high pressure gas. This
gas flows through the metal tubing to the CONDENSER COIL (3A) and
(3B) and RECEIVER (4).
|