|
|
TM5-4120-383-14
REFRIGERATION CYCLE.-Continued
1-8.
b. Bypass System. This unit has a bypass system which allows
cooling operation at low cooling loads without cycling the
In bypass the refrigerant is piped from the
compressor on and off.
discharge to the suction side of the compressor, bypassing the
EVAPORATOR COIL (9).
q When
the TEMPERATURE SELECTOR on the control module senses
that cooling conditions have reached the set point, it closes the
SOLENOID VALVE (7) to shut off refrigerant flow to the EVAPORATOR
COIL (9).
q As
the compressor suction pressure starts to drop, the
PRESSURE REGULATOR (11) opens to allow flow of hot gas from the
compressor.
q The
QUENCH VALVE (17) senses the temperature of the gas at
the suction side of the compressor. To prevent excessively hot gas
from reaching the compressor the QUENCH VALVE (17) opens to allow
liquid refrigerant to mix with the hot gas.
q The
LINEAR ACTUATING CYLINDER ASSEMBLY (15) automatically
controls the condenser discharge louver assembly.
q The
SERVICE VALVES (12) are provided for charging, and
general servicing of the high and low pressure sides of the
refrigerant system.
q The
LOW PRESSURE SWITCH (18), the HIGH PRESSURE SWITCH (14)
and the PRESSURE RELIEF VALVE (13) are provided to protect the unit
from damage due to pressure extremes.
q The
flexible METAL HOSE ASSEMBLIES (2) and (19) provide
vibration isolation between the compressor and other components of
the refrigeration system.
HEATING.
a. When the MODE SELECTOR is set for HIGH heat, all heating
elements, located behind the evaporator coil are energized. These
elements are protected from overheating by a thermal cutout switch.
Half of the elements are thermostatically controlled by the
TEMPERATURE SELECTOR. The remaining half are on all of the time.
When set for LOW, only the thermostatically controlled elements are
energized.
b. The two speed fan can be set for either HIGH or LOW
operation during heating.
1-12
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |