|
|
TM5-4120-383-14
INDICATORS.
(See fig. 2-2.)
The refrigerant sight glass is the only visual indicator
incorporated in the Model F9000H-3S air conditioner. The
refrigerant sight glass has a small chamber with a glass window
It is
through which the refrigerant condition can be observed.
installed in the liquid refrigerant line downstream from the
condenser coil. Liquid refrigerant actually flows through the
sight glass chamber only during cooling cycles when the air
conditioner is in operation in the COOL mode. The unit must be
operated approximately 15 minutes at maximum cooling prior to
checking condition of refrigerant at sight glass. The sight glass
is equipped with a center indicator that is moisture sensitive.
Dry refrigerant is indicated by green, it turns to chartreuse when
the moisture content becomes undesirable, and to yellow when the
level becomes unacceptable. Excessive moisture in the refrigerant
may damage or possibly destroy the compressor.
If the liquid
refrigerant observed in the sight glass has a milky appearance or
frequent bubbles appear, the volume of refrigerant is low and the
system should be charged. Either moisture or low charge
indications should be reported to direct support maintenance for
appropriate refrigeration system action.
Do not operate the air conditioner in the COOL mode
if the refrigerant color has reached the yellow band
or if numerous bubbles appear in the sight glass.
COOL mode operation may be continued with the
refrigerant color in the chartreuse band or with only
an occasional bubble appearing in the window, but the
sight glass should be rechecked after each four hours
of operation to insure that the condition has not
become worse.
2-5
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |