ORGANIZATIONAL PREVENTIVE MAINTENANCE
Table 4-1.
CHECKS AND SERVICES (PMCS)
QUARTERLY SCHEDULE-Continued
Para
Item to be
Item
Procedures
Ref.
No.
Inspected/Serviced
a. Check operation of louvers for
4-14
5
Conditioned Air
stiffness or binding.
Supply Louver
b. Remove, clean, inspect, repair,
and lubricate as necessary.
c. Set aside for the present and
reinstall after item 8.
a. Remove, clean, and inspect
4-16
6
Mist Eliminator
top front cover. Set aside for
present and reinstall after
item 8.
b. Remove, clean, inspect, and
service mist eliminator.
c. Replace mist eliminator if
it is damaged.
d. set aside for the present and
reinstall after item 8.
Compressed air used for
cleaning purposes will
not exceed  2 30 psi
(2.1 kg/cm ).
a. BlOW accumulated dust and
4-37
7
dirt out of air passages in
evaporator coil using compress-
ed air or the discharge side
of a portable vacuum cleaner.
Blow from front to back in
opposite direction from
operational airflow.
b.
Inspect coil for obvious
damage and all mounting hard-
ware for tightness and
security.
4-23