TM5-4120-383-14
ORGANIZATIONAL PREVENTIVE MAINTENANCE
Table 41.
CHECKS AND SERVICES (PMCS)
QUARTERLY SCHEDULEContinued
Para
Item
Item to be
Ref.
Procedures
No.
Inspected/Serviced
8
4-35
Heating Elements
a. Wipe or vacuum any remaining
dust or dirt from heating
elements, heater thermostat,
and all other components
and surfaces in the area.
NOTE
Use a clean, dry cloth (or
one slightly moistened
with water) for all wiping
operations. NEVER use an
oily or greasy cloth, any
oily residue left on any
surface will attract and
accumulate much more dust
and dirt than dry surfaces.
b. Inspect heating elements and
thermostat for obvious damage
and all mounting hardware for
tightness and security.
c. Inspect wiring harness for
damage or chafing and all
electrical connections for
tightness.
d. Install mist eliminator,
conditioned air supply
louver, and top front cover.
4-12
9
a. Remove, clean, inspect, and
Fresh Air
service.
Ventilation Guard
b. Discard and obtain replacement
if damaged.
c. Reinstall.
4-24
|