TM5-4120-383-14
ORGANIZATIONAL PREVENTIVE MAINTENANCE
Table 4-1.
CHECKS AND SERVICES (PMCS)
QUARTERLY SCHEDULE-Continued
Para
Item to be
Item
Procedures
Ref.
No.
Inspected/Serviced
10
4-12
a. Remove, clean, inspect, and
Condenser Air
repair guard, as necessary.
Inlet Guard
b. Place guard aside for the
present and reinstall after
item 14.
Compressed air used for
cleaning purposes will
not exceed 2 30 psi
(2.1 kg/cm ).
11
4-40
a. Blow accumulated dust and dirt
Condenser Coil
out of air passages in
condenser coil using compressed
air or the discharge side of a
portable vacuum cleaner. Blow
from inside for reverse airflow
direction.
b. Inspect coil for obvious
damage and all mounting hard-
ware for tightness and
security.
12
4-36
a. Wipe or vacuum dust and
Condenser Fan
dirt from fan and motor and
and Motor
all other components and sur-
faces in the immediate area.
b. Inspect fan for damage or bent
blades, motor for signs of
overheating, and all mounting
hardware for tightness and
security.
c. Inspect wiring harness for
damage or chafing and all
electrical connections for
tightness.
4-25
|