TM5-4120-383-14
ORGANIZATIONAL PREVENTIVE MAINTENANCE
Table 4-1.
CHECKS AND SERVICES (PMCS)
QUARTERLY SCHEDULE-Continued
Para
Item to be
Item
Ref.
Procedures
Inspected/Serviced
No.
13
a. Wipe or vacuum dust or dirt
Compressor
from the compressor canister
and remaining components
and surfaces in the lower
section of the cabinet.
heater element for signs of
4-31
c. Inspect wiring harness for
damage or chafing and all
electrical connections for
tightness.
d. Check all mounting hardware
for damage or chafing.
4-17
14
a. Check all mounting hardware
and linkage connections for
charge Air
tightness.
Louver and
Actuator
b. Clean and lubricate as
necessary.
c. Install condenser air inlet
guard and top rear cover.
4-15,
15
a. Wipe all surfaces clean.
Covers, Name-
4-11,
plates and
and
b. Check that all Warning and
Housing
4-41
instruction plates are in
place and legible.
c. Replace missing or illegible
plates.
d. Check that all covers are in
place, that there is no missing
or loose hardware and no dents,
breaks, or damage that would
be a hazard or interfere with
unit operation.
4-26