TM5-4120-383-14
4-16.
MIST ELIMINATOR.-Continued
(2) Agitate until dirt is removed, using a soft brush if
necessary to loosen caked-on dirt.
(3) Rinse in clean water or clean dry cleaning solvent.
(4) Drain, then hold horizontal and tap each edge on bench or
floor to dislodge droplets.
Inspect.
c.
(1) Inspect for damage such as perforations or punctures in
the screen and aluminum.
(2) Inspect for packed or crushed material that would reduce
airflow.
(3) Check for deformation of frame.
Straighten if possible
without crushing aluminum.
(4) Replace if crushed, punctured, badly deformed, or broken.
(5) Replace rubber insulation strip across top of mist
eliminator if it is missing or damaged.
d.
Installation.
(1) TOP marking must be up and airflow arrows, located on
side or bottom, must point outward away from coil.
(2) Slide mist eliminator down into mounting frames observing
air flow arrows and top marking.
(3) Install top front cover and secure with eight screws.
(4) Connect power at power source.
CONDENSER AIR DISCHARGE LOUVER AND LINKAGE.
This louver is located at the right rear of the unit and is
automatically operated by a refrigerant pressure actuated cylinder
and a push-pull cable.  The louvers open as refrigerant pressure in
the condenser coil increases.  This causes the louver to open more
fully to increase the flow of cooler air across the condenser coil.
4-48